Texas home inspection checklist (TREC Standards of Practice)

Every Texas licensed inspector must follow the TREC Standards of Practice set out in 22 TAC §§535.227–535.233. This page turns those rules into a working checklist: each section below lists what the rule requires you to inspect, report, or report as deficient, with its exact rule reference.

This checklist is a working document structured from the cited Standards of Practice. It does not replace the applicable Standard of Practice, nor any report form required by your state. You are responsible for your inspection and your report — your license is on the line.
Texas inspectors must deliver their report on the TREC Property Inspection Report Form (REI 7-6). This checklist is a working document — it is not the report form.
Standard: Texas Standards of Practice — 22 TAC §§535.227–535.233
Official source: Texas Real Estate Commission (trec.texas.gov)
Every section verified against the source on: September 12, 2026

1. General requirements

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.227(c) — verified September 12, 2026

The inspector shall

Operate fixed or installed equipment and appliances in at least one mode with ordinary controls at typical settings
Visually inspect accessible systems and components from near proximity, and from the interior of the attic and crawl spaces
Complete the standard inspection report form as required by §535.222 and §535.223

2. Foundations

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(a) — verified September 12, 2026

Report

Render a written opinion as to the performance of the foundation
Report the type of foundation(s)
Report the vantage point from which the crawl space was inspected
Generally report present and visible indications used to render the opinion of adverse performance: binding, out-of-square or non-latching doors; framing or frieze board separations; sloping floors; window, wall, floor or ceiling cracks or separations; rotating, buckling, cracking or deflecting masonry cladding

Report as deficient

Deteriorated materials
Deficiencies in foundation components such as beams, joists, bridging, blocking, piers, posts, pilings, columns, sills or subfloor
Deficiencies in retaining walls related to foundation performance
Exposed or damaged reinforcement
Crawl space ventilation that is not performing
Crawl space drainage that is not performing
Not required by §535.228(a) — do not present these as inspection items
  • Enter a crawl space or any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high
  • Provide an exhaustive list of indicators of possible adverse performance
  • Inspect retaining walls not related to foundation performance

3. Grading and drainage

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(b) — verified September 12, 2026

Report as deficient

Drainage around the foundation that is not performing
Deficiencies in grade levels around the foundation
Deficiencies in installed gutter and downspout systems
Not required by §535.228(b) — do not present these as inspection items
  • Inspect flatwork or detention/retention ponds (except as related to slope and drainage)
  • Determine area hydrology or the presence of underground water
  • Determine the efficiency or performance of underground or surface drainage systems

4. Roof covering materials

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(c) — verified September 12, 2026

The inspector shall

Inspect the roof covering materials from the surface of the roof

Report

Type of roof coverings
Vantage point from where the roof was inspected
Evidence of water penetration
Evidence of previous repairs to the roof covering material, flashing details, skylights and other roof penetrations

Report as deficient — deficiencies in

Fasteners
Adhesion
Roof covering materials
Flashing details
Skylights
Other roof penetrations
Not required by §535.228(c) — do not present these as inspection items
  • Inspect the roof from the roof level if it cannot be safely reached or staying on it is unsafe, or if walking it may significantly damage the roof covering
  • Determine the remaining life expectancy of the roof covering or the number of layers
  • Identify latent hail damage
  • Exhaustively examine all fasteners and adhesion
  • Provide an exhaustive list of locations of deficiencies and water penetrations

5. Roof structures and attics

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(d) — verified September 12, 2026

Report

The vantage point from which the attic space was inspected
Approximate average depth of attic insulation
Evidence of water penetration

Report as deficient

Attic space ventilation that is not performing
Deflections or depressions in the roof surface as related to adverse performance of the framing and decking
Missing insulation
Deficiencies in installed framing members and decking
Deficiencies in attic access ladders and access openings
Deficiencies in attic ventilators
Not required by §535.228(d) — do not present these as inspection items
  • Enter attics or unfinished spaces where openings are less than 22 by 30 inches or headroom is less than 30 inches
  • Operate powered ventilators
  • Provide an exhaustive list of locations of deficiencies and water penetrations

6. Interior walls, ceilings, floors, and doors

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(e) — verified September 12, 2026

Report

Evidence of water penetration

Report as deficient

Deficiencies in the condition and performance of doors and hardware
Deficiencies related to structural performance or water penetration
The absence of or deficiencies in fire separation between the garage and the living space and between the garage and its attic
Not required by §535.228(e) — do not present these as inspection items
  • Report cosmetic damage or the condition of floor, wall, or ceiling coverings; paints, stains, or other surface coatings; cabinets; or countertops
  • Provide an exhaustive list of locations of deficiencies and water penetrations

7. Exterior walls, doors, and windows

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(f) — verified September 12, 2026

Report

Evidence of water penetration

Report as deficient

The absence of performing emergency escape and rescue openings in all sleeping rooms
An attached garage doorway that is not equipped with self-closing or automatic closing devices
A door between the residence and an attached garage that is not a qualifying door (solid wood or solid honeycomb core steel at least 1-3/8 inches thick, or a 20-minute fire-rated door)
Missing or damaged screens
Deficiencies related to structural performance or water penetration
Deficiencies in weather stripping, gaskets or other air barrier materials
Deficiencies in claddings
Deficiencies in water resistant materials and coatings
Deficiencies in flashing details and terminations
Deficiencies in the condition and performance of exterior doors, garage doors and hardware
Deficiencies in the condition and performance of windows and components
Not required by §535.228(f) — do not present these as inspection items
  • Report the condition of awnings, blinds, shutters, security devices, or other non-structural systems
  • Determine the cosmetic condition of paints, stains, or other surface coatings
  • Operate a lock if the key is not available
  • Provide an exhaustive list of locations of deficiencies and water penetrations

8. Exterior and interior glazing

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(g) — verified September 12, 2026

Report as deficient

Insulated windows that are obviously fogged or display other evidence of broken seals
Deficiencies in glazing, weather stripping and glazing compound in windows and doors
The absence of safety glass in hazardous locations
The absence of fall protection at windows located less than 24 inches from the finished floor and greater than 72 inches from the finished grade
Not required by §535.228(g) — do not present these as inspection items
  • Exhaustively inspect insulated windows for evidence of broken seals
  • Exhaustively inspect glazing for identifying labels
  • Identify specific locations of damage

9. Interior and exterior stairways

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(h) — verified September 12, 2026

Report as deficient

Spacing between intermediate balusters, spindles, or rails that permits passage of an object greater than 4 inches in diameter (on the open side of staircase treads, spheres less than 4-3/8 inches may pass)
Deficiencies in steps, stairways, landings, guardrails, and handrails
Not required by §535.228(h) — do not present these as inspection items
  • Exhaustively measure every stairway component

10. Fireplaces and chimneys

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(i) — verified September 12, 2026

Report as deficient

Built-up creosote in accessible areas of the firebox and flue
The presence of combustible materials in near proximity to the firebox opening
The absence of fireblocking at the attic penetration of the chimney flue, where accessible
Deficiencies in the damper
Deficiencies in the lintel, hearth, hearth extension, and firebox
Deficiencies in a gas fixture installed in the fireplace not associated with the gas distribution system
Deficiencies in the circulating fan
Deficiencies in combustion air vents
Deficiencies in the chimney structure, termination, coping, crown, caps, and spark arrestor
Not required by §535.228(i) — do not present these as inspection items
  • Verify the integrity of the flue
  • Perform a chimney smoke test
  • Determine the adequacy of the draft

11. Porches, balconies, decks, and carports

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.228(j) — verified September 12, 2026

The inspector shall inspect

Attached balconies, carports, and porches
Abutting porches, decks, and balconies that are used for ingress and egress

Report as deficient

On decks 30 inches or higher above adjacent grade, spacings between intermediate balusters, spindles, or rails that permit passage of an object greater than four inches in diameter
Deficiencies in accessible components
Not required by §535.228(j) — do not present these as inspection items
  • Exhaustively measure every porch, balcony, deck, or attached carport component
  • Enter any area where headroom is less than 18 inches or the access opening is less than 24 inches wide and 18 inches high

12. Electrical — service entrance and panels

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.229(a) — verified September 12, 2026

Report as deficient

A drop, weatherhead or mast that is not securely fastened to the building
The absence of or deficiencies in the grounding electrode system
Missing or damaged dead fronts or cover plates
Conductors not protected from the edges of electrical cabinets, gutters, or cutout boxes
Electrical cabinets and panel boards not appropriate for their location (clothes closet, bathrooms, or exposed to physical damage)
Electrical cabinets and panel boards that are not accessible or lack a minimum of 36 inches of clearance in front of them
Deficiencies in electrical cabinets, gutters, cutout boxes, and panel boards
Deficiencies in the insulation of the service entrance conductors, drip loop, separation of conductors at weatherheads, and clearances
Deficiencies in the compatibility of overcurrent devices and conductors
Deficiencies in the overcurrent device and circuit for labeled and listed 250 volt appliances
Deficiencies in bonding and grounding
Deficiencies in conductors
Deficiencies in the operation of installed ground-fault or arc-fault circuit interrupter devices
The absence of trip ties on 250 volt overcurrent devices or multi-wire branch circuits
The absence of appropriate connections
The absence of anti-oxidants on aluminum conductor terminations
The absence of a main disconnecting means
Not required by §535.229(a) — do not present these as inspection items
  • Determine present or future sufficiency of service capacity amperage, voltage, or the capacity of the electrical system
  • Conduct voltage drop calculations
  • Determine the accuracy of overcurrent device labeling
  • Remove covers where hazardous as judged by the inspector
  • Verify the effectiveness of overcurrent devices
  • Operate overcurrent devices

13. Electrical — branch circuits, connected devices, and fixtures

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.229(b) — verified September 12, 2026

The inspector shall

Manually test the installed and accessible smoke and carbon monoxide alarms
Report the type of branch circuit conductors

Report as deficient — absence of GFCI protection in

Bathroom receptacles
Garage and accessory building receptacles
Outdoor receptacles
Crawl space receptacles and lighting outlets
Basement receptacles
Receptacles that serve kitchen countertops
Receptacles located within six feet of the outside edge of a sink, shower, or bathtub
Laundry area receptacles
Indoor damp and wet location receptacles
Kitchen dishwasher receptacle
Electrically heated floors

Report as deficient — absence of arc-fault protection in

Kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, and laundry areas

Report as deficient — other

The failure of operation of ground-fault circuit interrupter protection devices
Missing or damaged receptacle, switch or junction box covers
The absence of equipment disconnects
The absence of appropriate connections (copper/aluminum approved devices) if branch circuit aluminum conductors are discovered by random sampling
Receptacles less than five and a half feet above the floor that are not tamper resistant
Deficiencies in 125 volt receptacles: presence of power, correct polarity, presence of grounding
Deficiencies in 250 volt receptacles: presence of power
Deficiencies in switches
Deficiencies in bonding or grounding
Deficiencies in wiring, wiring terminations, junction boxes, devices, and fixtures, including improper location
Deficiencies in doorbell and chime components
Deficiencies in smoke and carbon monoxide alarms
Improper use of extension cords
Deficiencies in or absences of conduit, where applicable
The absence of smoke alarms in each sleeping room, outside each separate sleeping area, and in the living space of each story
The absence of carbon monoxide alarms outside each separate sleeping area when fuel-fired appliances are installed or the dwelling has an attached garage with an opening into the dwelling unit
Not required by §535.229(b) — do not present these as inspection items
  • Inspect low voltage wiring
  • Disassemble mechanical appliances
  • Verify the effectiveness of smoke alarms
  • Verify interconnectivity of smoke alarms
  • Activate smoke or carbon monoxide alarms that are or may be monitored or require the use of codes
  • Verify that smoke alarms are suitable for the hearing-impaired
  • Remove the covers of junction, fixture, receptacle or switch boxes unless specifically required
  • Test arc-fault circuit interrupter devices when the property is occupied or damage to personal property may result, in the inspector's reasonable judgment

14. Heating equipment

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.230(a) — verified September 12, 2026

Report

The type of heating system(s)
The energy source(s)

Report as deficient — general

Inoperative units
Deficiencies in the thermostats
Inappropriate location
The lack of protection from physical damage
Burners, burner ignition devices or heating elements, switches, and thermostats less than 18 inches above the lowest garage floor elevation, unless the unit is listed for garage floor installation
The absence of an opening allowing access to equipment for inspection, service, repair or replacement without removing permanent construction
When applicable, a floored passageway and service platform allowing access for equipment inspection, service, repair or replacement
Deficiencies in mounting and performance of window and wall units

Report as deficient — electric units

Deficiencies in performance of heat pumps
Deficiencies in performance of heating elements
Deficiencies in condition of conductors

Report as deficient — gas units

Gas leaks in the heating equipment not associated with the gas distribution system
Flame impingement, uplifting flame, improper flame color, or excessive scale buildup
Deficiencies in combustion and dilution air
Deficiencies in the vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances

15. Cooling equipment

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.230(b) — verified September 12, 2026

Report

The type of system(s)
Measure and report the temperature difference between supply air and return air, or report the industry-accepted method used to determine performance
Generally report extraneous factors or conditions present on the day of the inspection that would adversely impact the temperature differential of an otherwise performing unit

Report as deficient

Inoperative units
Performance that fails to achieve a 15 to 22 degrees Fahrenheit temperature differential, or fails to cool adequately by other industry-accepted methods
The absence of an opening allowing access to equipment without removing permanent construction
When applicable, the absence of a floored passageway and service platform
Noticeable vibration of blowers or fans
Water in the auxiliary/secondary drain pan
A primary drain pipe that discharges in a sewer vent
Missing or deficient refrigerant pipe insulation
Dirty coils, where accessible
Condensing units lacking adequate clearances or air circulation, or with deficiencies in the fins, location, levelness, or elevation above grade
Deficiencies in the condensate drain and auxiliary/secondary pan and drain system
Deficiencies in mounting and performance of window or wall units
Deficiencies in thermostats

Evaporative coolers — report

The type of system and the type of water supply line

Evaporative coolers — report as deficient

Inoperative units
Inadequate access and clearances
Deficiencies in performance or mounting
Missing or damaged components
The presence of active water leaks
The absence of backflow prevention

16. Duct systems, chases, and vents — and HVAC limitations

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.230(c)–(d) — verified September 12, 2026

Report as deficient

Damaged duct systems or improper material
Damaged or missing duct insulation
The absence of air flow at accessible supply registers
The presence of gas piping and sewer vents concealed in ducts, plenums and chases
Ducts or plenums in contact with earth
Deficiencies in filters
Deficiencies in grills or registers
Deficiencies in the location of return air openings
Not required by §535.230(c)–(d) — do not present these as inspection items
  • Program digital thermostats or controls
  • Inspect for refrigerant pressure, type of refrigerant, or refrigerant leaks
  • Inspect winterized or decommissioned equipment
  • Inspect duct fans, humidifiers, dehumidifiers, air purifiers, motorized dampers, electronic air filters, multi-stage controllers, sequencers, heat reclaimers, wood burning stoves, boilers, oil-fired units, supplemental heating appliances, de-icing provisions, or reversing valves
  • Operate setback features on thermostats or controls
  • Operate radiant heaters, steam heat systems, or unvented gas-fired heating appliances
  • Operate cooling equipment when outdoor temperature is below 60°F, or heat pumps in heat pump mode when outdoor temperature is above 70°F
  • Verify compatibility of components, tonnage and manufacturer match of coils, accuracy of thermostats, or integrity of the heat exchanger
  • Determine sizing, efficiency, or adequacy of the system, balanced air flow, or types of materials contained in insulation

17. Plumbing systems

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.231(a) — verified September 12, 2026

Report

Location of water meter
Location of homeowner's main water supply shutoff valve
Static water pressure
Visible material used for water supply lines and drain lines

Report as deficient

The presence of active leaks
Water pressure exceeding 80 PSI
The lack of a pressure reducing valve when water pressure exceeds 80 PSI
The lack of a visible expansion tank when a pressure reducing valve, check valve, or backflow preventer is in place
The absence of fixture shutoff valves
The absence of dielectric unions, when applicable
The absence of back-flow devices, anti-siphon devices, or air gaps at the flow end of fixtures
Deficiencies in water supply pipes and waste pipes
Deficiencies in the installation and termination of the vent system
Deficiencies in the performance of fixtures and faucets not connected to an appliance
Deficiencies in water supply, as determined by viewing functional flow in two fixtures operated simultaneously
Deficiencies in fixture drain performance
Deficiencies in orientation of hot and cold faucets
Deficiencies in installed mechanical drain stops
Deficiencies in commodes, fixtures, showers, tubs, and enclosures
Deficiencies in the condition of the gas distribution system
Not required by §535.231(a) — do not present these as inspection items
  • Operate any main, branch, or shut-off valves
  • Operate or inspect sump pumps or waste ejector pumps
  • Verify the performance of the bathtub overflow, clothes washing machine drains or hose bibbs, or floor drains
  • Inspect any system that has been winterized, shut down or otherwise secured
  • Inspect circulating pumps, free-standing appliances, solar water heating systems, water-conditioning equipment, filter systems, water mains, private water supply systems, water wells, pressure tanks, sprinkler systems, swimming pools, or fire sprinkler systems
  • Inspect inaccessible gas supply system components for leaks
  • Inspect for sewer clean-outs or for the presence or performance of private sewage disposal systems
  • Determine quality, potability, or volume of the water supply, or effectiveness of backflow or anti-siphon devices

18. Water heaters

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.231(b) — verified September 12, 2026

Report

The energy source
The capacity of the unit(s)

Report as deficient

Inoperative units
Leaking or corroded fittings or tanks
Damaged or missing components
The absence of a cold water shutoff valve
If applicable, the absence of a pan or a pan drain system that does not terminate over a waste receptor or to the exterior above the ground surface
Inappropriate locations
The lack of protection from physical damage
Burners, burner ignition devices or heating elements, switches, or thermostats less than 18 inches above the lowest garage floor elevation, unless listed for garage floor installation
The absence of an opening allowing access to equipment without removing permanent construction
When applicable, the absence of a floored passageway and service platform
The absence of or visible deficiencies in the temperature and pressure relief valve and discharge piping
A temperature and pressure relief valve that failed to operate, when tested manually

Electric units — report as deficient

Deficiencies in performance of heating elements
Deficiencies in condition of conductors

Gas units — report as deficient

Gas leaks in the water heater not associated with the gas distribution system
Flame impingement, uplifting flame, improper flame color, or excessive scale build-up
Deficiencies in combustion and dilution air
Deficiencies in vent pipe, draft hood, draft, proximity to combustibles, and vent termination point and clearances
Not required by §535.231(b) — do not present these as inspection items
  • Verify the effectiveness of the temperature and pressure relief valve, discharge piping, or pan drain pipes
  • Operate the temperature and pressure relief valve if operation may cause damage to persons or property
  • Determine the efficiency or adequacy of the unit

19. Hydro-massage therapy equipment

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.231(c) — verified September 12, 2026

Report as deficient

Inoperative units
The presence of active leaks
Deficiencies in components and performance
Missing and damaged components
The absence of an opening allowing access to equipment without removing permanent construction
The absence or failure of operation of ground-fault circuit interrupter protection devices
Not required by §535.231(c) — do not present these as inspection items
  • Determine the adequacy of self-draining features of circulation systems

20. Gas distribution systems

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.231(d) — verified September 12, 2026

Report

Location of gas meter
Visible material used for the gas distribution system

Report as deficient

Noticeable gas leaks
The absence of a gas shutoff valve within six feet of the appliance
The absence of a gas appliance connector or one that exceeds six feet in length
Gas appliance connectors concealed within or extended through walls, floors, partitions, ceilings or appliance housings
Deficiencies in gas shutoff valves
Deficiencies in access to gas shutoff valves that prohibits full operation
Deficiencies in gas appliance connector materials
Deficiencies in the condition and type of gas distribution lines and fittings
Lack of visible bonding on the gas distribution system, including corrugated stainless steel tubing (CSST)
Lack of visible sediment traps
Not required by §535.231(d) — do not present these as inspection items
  • Inspect sacrificial anode bonding or for its existence
  • Pressurize or test the gas system, drip legs or shutoff valves
  • Operate gas line shutoff valves
  • Light or ignite pilot flames

21. Appliances

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.232 — verified September 12, 2026

Dishwashers — report as deficient

Inoperative units
Deficiencies in performance or mounting
Rusted, missing or damaged components
The presence of visible active water leaks
The absence of visible backflow prevention

Food waste disposers — report as deficient

Inoperative units
Deficiencies in performance or mounting
Missing or damaged components
The presence of visible active water leaks

Range hoods and exhaust systems — report as deficient

Inoperative units
Deficiencies in performance or mounting
Missing or damaged components
Ducts that do not terminate outside the building, if not of a re-circulating type
Improper duct material

Ranges, cooktops, and ovens — report as deficient

Inoperative units
Missing or damaged components
Combustible material within thirty inches above the cook top burners
Absence of an anti-tip device, if applicable
Gas leaks in the gas range, cooktops and ovens not associated with the gas distribution system
Deficiencies in thermostat accuracy (within 25°F at a setting of 350°F)
Deficiencies in mounting and performance

Microwave ovens (built-in) — report as deficient

Inoperative units
Deficiencies in performance or mounting
Missing or damaged components

Mechanical exhaust systems and bathroom heaters — report as deficient

The lack of mechanical ventilation in a bathroom if no operable window is present
Inoperative units
Deficiencies in performance or mounting
Missing or damaged components
Ducts that do not terminate outside the building
A gas heater that is not vented to the exterior unless listed as an unvented type

Garage door operators — report as deficient

Inoperative units
Deficiencies in performance or mounting
Missing or damaged components
Installed photoelectric sensors located more than six inches above the garage floor
Deficiencies in performance or absence of auto reversing mechanisms and manual detachment device
Door locks or side ropes that have not been removed or disabled

Dryer exhaust systems — report as deficient

Missing or damaged components
The absence of a dryer exhaust system when provisions are present for a dryer
Ducts that do not terminate to the outside of the building
Screened terminations
Ducts that are not made of metal with a smooth interior finish
Not required by §535.232 — do not present these as inspection items
  • Operate or determine the condition of other auxiliary components of inspected items
  • Test for microwave oven radiation leaks
  • Inspect self-cleaning functions
  • Disassemble appliances
  • Determine the adequacy of venting systems
  • Determine proper routing and lengths of duct systems
  • Operate or determine the condition of clothes washer, clothes dryer, or refrigerator
  • Operate or determine the condition of other built-in appliances, except as provided under §535.233(h)

22. Optional systems — scope

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(a)–(b) — verified September 12, 2026

An inspector is NOT required to inspect the systems described in §535.233. If the inspector agrees to inspect one of them, the general provisions of §535.227 and the specific requirements of §535.233 for that system apply. The six sections below detail those conditional requirements; they are marked OPTIONAL because the inspection itself is not required.

23. OPTIONAL — Landscape irrigation (sprinkler) systems

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(c) — verified September 12, 2026

The inspector shall

Manually operate all zones or stations on the system through the controller

Report as deficient

The absence of a rain or moisture sensor
Inoperative zone valves
Surface water leaks
The absence of a backflow prevention device
The absence of shutoff valves between the water meter and backflow device
Deficiencies in the performance and mounting of the controller
Missing or damaged components
Deficiencies in the performance of the water emission devices (sprayer heads, rotary sprinkler heads, bubblers or drip lines)
Not required by §535.233(c) — do not present these as inspection items
  • Inspect for effective coverage of the irrigation system
  • Inspect the automatic function of the controller
  • Inspect the effectiveness of the sensors (rain, moisture, wind, flow or freeze)
  • Determine sizing and effectiveness of the backflow prevention device
  • Report on the performance of an underground zone

24. OPTIONAL — Swimming pools, spas, hot tubs, and equipment

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(d) — verified September 12, 2026

Report

The type of construction

Report as deficient

The presence of a single blockable main drain (potential entrapment hazard)
A pump motor, blower, or other electrical equipment that lacks bonding
The absence of or deficiencies in safety barriers
Water leaks in above-ground pipes and equipment
The absence or failure in performance of ground-fault circuit interrupter protection devices
Deficiencies in surfaces
Deficiencies in tiles, coping, and decks
Deficiencies in slides, steps, diving boards, handrails, and other equipment
Deficiencies in drains, skimmers, and valves
Deficiencies in filters, gauges, pumps, motors, controls, and sweeps
Deficiencies in lighting fixtures
Deficiencies in the pool heater that these standards require to be reported for the heating system
Not required by §535.233(d) — do not present these as inspection items
  • Disassemble filters or dismantle or open any components or lines
  • Operate valves
  • Uncover or excavate any lines or concealed components of the system
  • Fill the pool, spa, or hot tub with water
  • Inspect any system that has been winterized, shut down, or otherwise secured
  • Determine the presence of sub-surface water tables
  • Determine the effectiveness of entrapment covers
  • Determine the presence of pool shell or sub-surface leaks
  • Inspect ancillary equipment (computer controls, covers, chlorinators or other chemical dispensers, water ionization devices or conditioners) other than required by this section

25. OPTIONAL — Outbuildings

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(e) — verified September 12, 2026

Report as deficient

The absence or failure in performance of ground-fault circuit interrupter protection devices in grade-level portions of unfinished accessory buildings used for storage or work areas, boathouses, and boat hoists
Deficiencies in the structural, electrical, plumbing, heating, ventilation, and cooling systems that these standards require to be reported for the principal building

26. OPTIONAL — Private water wells

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(f) — verified September 12, 2026

The inspector shall

Operate at least two fixtures simultaneously
Recommend or arrange to have performed coliform testing

Report

The type of pump and storage equipment
The proximity of any known septic system

Report as deficient — deficiencies in

Water pressure and flow and performance of pressure switches
The condition of accessible equipment and components
The well head, including improper site drainage and clearances
Not required by §535.233(f) — do not present these as inspection items
  • Open, uncover, or remove the pump, heads, screens, lines, or other components of the system
  • Determine the reliability of the water supply or source
  • Locate or verify underground water leaks

27. OPTIONAL — Private sewage disposal systems

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(g) — verified September 12, 2026

Report

The type of system
The location of the drain or distribution field
The proximity of any known water wells, underground cisterns, water supply lines, bodies of water, sharp slopes or breaks, easement lines, property lines, soil absorption systems, swimming pools, or sprinkler systems

Report as deficient

Visual or olfactory evidence of effluent seepage or flow at the surface of the ground
Inoperative aerators or dosing pumps
Deficiencies in accessible components
Deficiencies in functional flow
Deficiencies in site drainage and clearances around or adjacent to the system
Deficiencies in the aerobic discharge system
Not required by §535.233(g) — do not present these as inspection items
  • Excavate or uncover the system or its components
  • Determine the size, adequacy, or efficiency of the system
  • Determine the type of construction used

28. OPTIONAL — Other built-in appliances

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233, §535.233(h) — verified September 12, 2026

Report

Deficiencies in condition or operation of other built-in appliances not listed under §535.232

General limitations — §535.227(d)

Source: Texas Standards of Practice — 22 TAC §§535.227–535.233 — verified September 12, 2026

The inspector is not required to:

How to use this checklist

Open it on any phone, tablet, or computer during the walkthrough. Mark each item OK (inspected, no deficiency observed), DEF (deficient — the finding goes in your report), or N/I (not inspected, with the reason in the section notes). Then print or save the page as a US Letter PDF: the printed document carries the standard's reference, the verification date, and the disclaimer. Nothing is stored anywhere — the page holds your marks only until you close it, which is the point: your working document leaves with you as a PDF.

The collapsed “Not required” block inside each section lists what the standard explicitly excludes. Those exclusions are part of the standard: they are shown so that no exclusion is ever mistaken for an inspection item, and so you can point a client to the exact limitation when a question comes up.

Frequently asked questions

Is this checklist the official TREC report form?

No. Texas requires inspectors to deliver their findings on the TREC Property Inspection Report Form (REI 7-6). This page is a working checklist structured from the Standards of Practice in 22 TAC §§535.227–535.233 — it helps you cover every required item during the walkthrough, but it is not the report form and does not replace it.

Which standard applies to home inspections in Texas?

The Texas Real Estate Commission Standards of Practice, 22 TAC §§535.227–535.233, in force since February 1, 2022. They define the minimum requirements for an inspection of a one-to-four family dwelling, and every section of this checklist carries its exact rule reference.

Do I have to inspect optional systems like pools or sprinklers?

No. Under §535.233 an inspector is not required to inspect optional systems such as landscape irrigation, swimming pools and spas, outbuildings, private water wells, or private sewage disposal systems. If you agree to inspect one, the specific requirements of §535.233 for that system apply.

Can I depart from a required inspection item?

Yes, within the limits of the departure provision in §535.227(f): client agreement, lack of qualification, conditions preventing inspection, hazard, risk of damage, or certain multi-family common elements. You must notify the client and note the reason on the inspection report form.

Does this tool store my inspection data?

No. Everything runs in your browser. Marks and notes exist only until you close the page — print or save the PDF before leaving. There is no account and no server storage.